Data Centre in London
We were asked to undertake a Protection and Grading Study, where the completed report would give its findings for a short circuit study to comply with BS EN 60909 while incorporating a Selectivity study for the electrical distribution system to the facility.
This study covered:
A visual survey upfront to identify relay/trip units and breaker types.
MV distribution including UKPN settings.
LV distribution
Generators
UPS
Focus on use of the type C or D MCB's.
The study provided a list of "Existing" settings with time-current curves.
Corrective actions list of proposed "New" settings with time-current curves.
For the study to be undertaken, a visual survey was required on the existing relays and protection settings at the site.
The survey covered :
ETAP Model single line diagram
Protection Settings Schedules
Co-ordination sheets (time current curves) for overcurrent and earth fault
Load Flow & Short circuit fault current results to BS EN 60909
Reference Documents
Protection setting Guide & Device Data
Network and Load Data
Cross referenced to the manufactures trip unit and relay characteristic curves. Cross referenced with Amtech Protect software.
PROJECT DETAILS
Client: Data Centre in London
Sector: Data Centre